<noframes id="rtnld">
    <listing id="rtnld"></listing>

      <form id="rtnld"><nobr id="rtnld"></nobr></form>

      Hello! welcomeZhejiang Xikai Electric Co. , Ltd.
      Zhejiang Xikai Electric Co. , Ltd.
      Contact
      Zhejiang Xikai Electric Co. , Ltd.
      Mailbox:wzxikai@wzxikai.com
      Tel:+86 577 61666 016
      address:No.271, Weishiqi Road, Yueqing Economic Development Insuatrial Zone, Yueqing, Zhejiang.

      product list

      Indoor high voltage load switch
      14/5000 Indoor vacuum circuit breaker
      Outdoor vacuum circuit breaker
      Outdoor high voltage load switch
      Outdoor high voltage disconnector
      Outdoor drop fuse
      High voltage current limiting fuse series
      High voltage complete set
      current position:Home>Product Center

      Product Center

        • FN7-12(24)Series Indoor Load Break Switch

        FN7-12(24)Series Indoor Load Break Switch

        FN7-12(24) is used for three-phase AC 50/60Hz 12kV, 24kV power systems. They used for breaking load current and controlling short-circuit current. FN7-12R type M.V load switch-fuse combination is based on the FN7-12 series M.V load switch, then put the operating mechanism on the side, as customer order

        Technical Information

        Technical Specification

         

         

         

         

         

        Rated voltage

        kV

         

        12

        24

        Rated current

        A

        400

         

        630

        630

        Rated power frequency

        Hz

        50/60

         

        50/60

        50/60

        Short circuit making capacity

        kA Peak.

        31.5

         

        50

        50

        Peak withstand current

        kA Peak.

        31.5

         

        50

        50

        Short time current

        kA eff.

         

         

         

         

        1Sec.

         

        25

         

        25

        25

        3Sec.

         

        12.5

         

        20

        20

        Max. breaking capacity in co-operation with fuses IEC 62271-105 (IEC 420 1990-11)

        A

        1600

         

        1600

        900

        Max. fuse current(XRNT Fuse)

        A

        200

         

        200

        200

        Power frequency withstand voltage 50Hz 1 min,:

         

         

         

         

         

        - To earth and between poles

        kV

        42

         

        42

        55

        - Across isolating distance

        kV

        48

         

        48

        70

        Impulse withstand voltage 1.2/50μ s:

         

         

         

         

         

        - To earth and between poles

        kV

        75

         

        75

        125

        - Across isolating distance

        kV

        85

         

        85

        145

        Mechanism Endurance

        cycles

        2000

         

        2000

        2000


        Overall and installation dimensions


        国产精品揄拍100视频