<noframes id="rtnld">
    <listing id="rtnld"></listing>

      <form id="rtnld"><nobr id="rtnld"></nobr></form>

      Hello! welcomeZhejiang Xikai Electric Co. , Ltd.
      Zhejiang Xikai Electric Co. , Ltd.
      Contact
      Zhejiang Xikai Electric Co. , Ltd.
      Mailbox:wzxikai@wzxikai.com
      Tel:+86 577 61666 016
      address:No.271, Weishiqi Road, Yueqing Economic Development Insuatrial Zone, Yueqing, Zhejiang.

      product list

      Indoor high voltage load switch
      14/5000 Indoor vacuum circuit breaker
      Outdoor vacuum circuit breaker
      Outdoor high voltage load switch
      Outdoor high voltage disconnector
      Outdoor drop fuse
      High voltage current limiting fuse series
      High voltage complete set
      current position:Home>Product Center

      Product Center

        • FKN12 Series Indoor Load Break Switch

        FKN12 Series Indoor Load Break Switch

        The switch disconnectors series FKN12 are increasingly adopted in MV installations, owing to their superior interrupting features and to their capability to withstand the short-circuit currents which occur mainly as consequences of faults in distribution networks. The versions combined with HRC fuses are particularly suitable for the protection of distribution transformers up to 1250 kVA The use of FKN12, designed for installation in compartmented switchboards have the following advantages: -Full segregation between the busbar compartment and the cable compartment, with switch disconnector in both "closed" and "open" position. -The moving contact, of the sliding vertical type, can be easily checked and cleaned with live bus-bars and earthing switch (ES) closed. -No adjustment is needed in the tripping mechanism of the switch fuse combination and of the ES: they are built together in a single unit, which is adjusted and checked during assembly in the factory, before the final test.

        Technical Information

        Technical Specification

         

         

        Rated voltage

        kV

        12

        Rated current

        A

        630

        Rated power frequency

        Hz

        50/60

        Short circuit making capacity

        kA Peak.

        67

        Peak withstand current

        kA Peak.

        82

        Short time current

        kA eff.

         

        1Sec.

         

        31.5

        2Sec.

         

        25

        3Sec.

         

        20

        Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11)

        A

        1600

        Max. fuse current(XRNT Fuse)

        A

        125

        Power frequency withstand voltage 50Hz 1 min,:

         

         

        - To earth and between poles

        kV

        42

        -Across isolating distance

        kV

        45

        Impulse withstand voltage 1.2/50μ s:

         

         

        - To earth and between poles

        kV

        75

        - Across isolating distance

        kV

        85

        Mechanism Endurance

        cycles

        2000


        Overall and installation dimensions

         