      Hello! welcomeZhejiang Xikai Electric Co. , Ltd.
      Zhejiang Xikai Electric Co. , Ltd.
      Contact
      Zhejiang Xikai Electric Co. , Ltd.
      Mailbox:wzxikai@wzxikai.com
      Tel:+86 577 61666 016
      address:No.271, Weishiqi Road, Yueqing Economic Development Insuatrial Zone, Yueqing, Zhejiang.

      product list

      Indoor high voltage load switch
      14/5000 Indoor vacuum circuit breaker
      Outdoor vacuum circuit breaker
      Outdoor high voltage load switch
      Outdoor high voltage disconnector
      Outdoor drop fuse
      High voltage current limiting fuse series
      High voltage complete set
      current position:Home>Product Center

      Product Center

        • FN18 High Voltage Indoor Load Break Switch

        FN18 High Voltage Indoor Load Break Switch

        FN18 is a general purpose, three-pole, load break switch that offers switchgear owners and assemblers the advantages of an advanced interrupting technology and proven, dependable performance in a compact design. The switch is available to switchgear assemblers as a building block for metal-enclosed and pad-mounted switchgear applications in ratings from 12 upto 24kV. The standard FN18 switch includes a heavy-duty steel frame with stand-off insulators, a unique puffer-type arc extinguishing system, an operating mechanism and current-carrying components, including blade-type interrupters with cast hinges and jaw connectors. Optional accessories and features include a variety of operating handles, a motor operator, auxiliary switches, a shunt trip device, fuse bases, mechanical fuse tripping, grounding switches, mechanical door interlocking and key interlocking.

        Technical Information

        Technical Specification

         

         

         

        Rated voltage

        kV

        12

        24

        Rated current

        A

        630

        630

        Rated power frequency

        Hz

        50/60

        50/60

        Short circuit making capacity

        kA Peak.

        50

        50

        Peak withstand current

        kA Peak.

        50

        50

        Short time current

        kA eff.

         

         

        1Sec.

         

        31.5

        25

        2Sec.

         

        25

        25

        3Sec.

         

        20

        16

        Max. breaking capacity in co-operation with fuses IEC 62271-105 (IEC 420 1990-11)

        A

        1600

        900

        Max. fuse current(XRNT Fuse)

        A

        200

        200

        Power frequency withstand voltage 50Hz 1 min,:

         

         

         

        - To earth and between poles

        kV

        42

        65

        - Across isolating distance

        kV

        48

        79

        Impulse withstand voltage 1.2/50μ s:

         

         

         

        - To earth and between poles

        kV

        75

        125

        - Across isolating distance

        kV

        85

        145

        Mechanism Endurance

        cycles

        2000

        2000


        Overall and installation dimensions