        • LW38-40.5 outdoor high voltage AC Sf6 circuit breaker

        LW38-40.5 outdoor high voltage AC Sf6 circuit breaker

        LW38-40.5 outdoor AC high voltage sulphur hexafluoride circuit breaker (hereinafter referred to as "circuit breaker") is an outdoor high-voltage power distribution switchgear with three-phase AC 50Hz and rated voltage of 40.5kV. It can be used to divide and match rated current and fault current, cast and cut capacitor group and conversion line. It is especially suitable for frequent operation or as a contact breaker. The circuit breaker uses SF6 gas as the arc extinguishing and insulating medium, and is installed outdoors. It adopts an elevated porcelain column structure. The circuit breaker complies with GB 1984-201 4 “High Voltage AC Circuit Breaker”, DL/T 402-2016 “High Voltage AC Circuit Breaker” and JB/T 9694-2008 “High Voltage AC Sulfur Hexafluoride Circuit Breaker” and other technical standards.

        Environmental Conditions

        1、 Altitude: no more than 1000m, if the altitude is higher than 1000m, the rated insulation level should be corrected accordingly;

        2、 Ambient temperature: upper limit +45℃ , lower limit -40℃ , maximum daily temperature difference of 25K;

        3、 Humidity: average daily relative humidity ≤ 95%, average monthly relative humidity ≤90%;

        4、Solar radiation intensity: ≥0.1W/cm2;

        5、Wind speed: 34m / s;

        6、Wind pressure: 700Pa;

        7、Pollution level: e level;

        8、Ice thickness: ≤10mm;

        9、 Tolerance to earthquake: horizontal acceleration 0.3g, vertical acceleration 0.2g



        Main Features

        1、 Using SF6 gas to extinguish arc and insulation, excellent insulation performance;

        2、The structure is simple, and the maintenance period is long;

        3、Strong breaking ability and long mechanical life;

        4、 Either built-in or external current transformer, high measurement accuracy;

        5、 Built-in intelligent wet temperature controller to ensure safe and reliable operation of circuit breakers in high and cold regions;

        6、 The overall sealing design of the housing has been improved to effectively prevent the bad weather caused by sandstorms and other bad weather.


        Technical Information

        Technical Specification

         

         

         

        Rated frequency

         

        Hz

        50

        Rated voltage

         

        kV

        40.5

        Rated current

         

        A

        1250、1600、2000

        Rated short-circuit breaking current

        kA

        31.5

        Rated short circuit closing current

        kA

        80

        Rated short-time withstand current

        kA

        31.5

        Rated peak withstand current

         

        kA

        80

        Rated out-of-step breaking current

        kA

        10

        Rated short circuit duration

         

        S

        4

        Rated short-circuit breaking current breaking times

        Times

        1 0

         

         

        Rated short-time power frequency withstand voltage

         

         

        Interphase and ground (dry test)

        kV/min

        95/1

         

        Fracture (dry test)

        kV/min

        118/1

         

        Phase to ground (wet test)

        kV/min

        80/1

         

        Auxiliary circuit to ground

        kV/min

        2/1

         

        Rated lightning impulse withstand voltage

         

        Phase to ground

        kV

        185

         

        Fracture

        kV

        215

        Rated operating voltage and auxiliary circuit rated voltage

        V

        AC220、DC220

        Main loop resistance

         

        Rated current 1600A and below

        μΩ

        ≤90

         

         

        1600A Rated current greater than 1600A

        ms

        ≤40

        Closing time

         

        Under AC voltage

        ms

        ≤100

         

         

        Under DC voltage

        ms

        55~100

        Opening time

         

        Under AC voltage

        ms

        ≤60

         

         

        Under DC voltage

        ms

        30~65



         

         

        Continued on the table

        Technical Specification

         

         

         

        Combined-minute time

         

        ms

        ≥120(Operating state) ≥120

        Split-time

         

        ms

        ≤50

        Full break time

         

        ms

        ≤78

        Rated operation sequence

         

        ms

        O-0.3S-CO-180s-CO

        Moving contact stroke

         

        mm

        96±2.5

        Contact opening distance

         

        mm

        60±1.5

        Closing buffer stroke

         

        mm

        10±2

        Phase-to-phase closure

         

        ms

        ≤3

        Phase-to-phase closure

         

        ms

        ≤3

        Phase spacing

         

        mm

        725

        SF6 annual air leak rate

         

        %

        ≤0.5

         

        SF6 gas moisture content (ppm, gauge pressure at 20 ℃)

        Handover acceptance value

        V/V

        ≤150

        Running value

        V/V

        ≤300

        SF6 gas rated pressure (20 ° C gauge pressure)

        Mpa

        0.45

        SF6 gas supplemental pressure (gauge pressure at 20 °C)

        Mpa

        0.42

        SF6 gas blocking pressure (gauge pressure at 20 ° C)

        Mpa

        0.4

        Mechanical life

         

        Times

        6000

        SF6 gas weight

         

        kg

        5

        Weight

        With CT

        kg

        800

         

        Without CT

        kg

        1000


        Download Google

        1、Please indicate the product name and model number;

        2、Please indicate the rated voltage, rated current and rated short-circuit breaking current;

        3、Please indicate the operating voltage of the operating mechanism and the auxiliary (control) circuit;

        4、Please indicate the number of current transformers, installation methods (built-in or external), ratio, accuracy and rated capacity;

        5、Please specify other special requirements, such as the type of cold, mounting brackets and the number of auxiliary contacts;

        6、Please indicate the order quantity and delivery time

        ?

        Overall and installation dimensions

         

        ?