        • FZW28-12 Outdoor AC high voltage boundar y vacuum load switch

        FZW28-12 Outdoor AC high voltage boundar y vacuum load switch

        FZW28-12 series outdoor AC high voltage boundary vacuum load switch is suitable for outdoor three-phase AC power distribution system with rated voltage of 12kV and rated frequency of 50Hz. It is used for opening and closing load current and closing short circuit current. Applicable to substations, industrial and mining enterprises and cities, agricultural networks for protection cities, agricultural network automation distribution network and frequent operations. The boundary load switch consists of two parts, the FZW28-12 vacuum load switch and the controller, which are electrically connected through an air socket and an outdoor sealed control cable. It can reliably judge the zero-sequence current and phase-to-phase short-circuit current of the milliampere inside and outside the detection circle, which can be suitable for the distribution system with different neutral grounding methods.

        Technical Information

        Technical Specification

         

         

         

        Rated voltage

         

         

        kV

        12

         

         

         

        dry

        kV

        42/48

         

         

        1min power frequency withstand voltage (interpole to ground / fracture)

        wet

         

        34

        Rated insulation level

         

        Lightning impulse withstand voltage (interpole to

         

        kV

        125/195

        Rated frequency

         

         

        Hz

        50

        Rated current

         

         

        A

        630

        Rated delay withstand current and duration

         

        kA/2s

        16

        Rated peak withstand current

         

        kA

        40

        Rated short circuit closing current

         

        kA

        40

        Mechanical life

         

         

        Times

        10000

        Net weight

         

         

        kg

        198