<noframes id="rtnld">
    <listing id="rtnld"></listing>

      <form id="rtnld"><nobr id="rtnld"></nobr></form>

      Hello! welcomeZhejiang Xikai Electric Co. , Ltd.
      Zhejiang Xikai Electric Co. , Ltd.
      Contact
      Zhejiang Xikai Electric Co. , Ltd.
      Mailbox:wzxikai@wzxikai.com
      Tel:+86 577 61666 016
      address:No.271, Weishiqi Road, Yueqing Economic Development Insuatrial Zone, Yueqing, Zhejiang.

      product list

      Indoor high voltage load switch
      14/5000 Indoor vacuum circuit breaker
      Outdoor vacuum circuit breaker
      Outdoor high voltage load switch
      Outdoor high voltage disconnector
      Outdoor drop fuse
      High voltage current limiting fuse series
      High voltage complete set
      current position:Home>Product Center

      Product Center

        • GW10-15 Outdoor High Voltage Ac Disconnector

        GW10-15 Outdoor High Voltage Ac Disconnector

        GW10-15 series outdoor high-voltage AC isolating switch (hereinafter referred to as "isolation switch") is a single-phase hook-bar operation type isolating switch, and the knife has self-locking device. The isolating switch is suitable for the isolation of 12kV and 15kV overhead lines, and is opened and closed under no load. It is widely used with circuit breakers or load switches to provide safe visible breaks for the line. The isolating switch complies with GB 1985-2014 "High Voltage AC Isolation Switch and Grounding Switch", DL/T 486-2010 "High Voltage AC Isolation Switch and Grounding Switch" and other technical standards.

        Technical Information

        Technical Specification

         

         

         

        Rated frequency

         

        Hz

        50

        Rated voltage

         

        kV

        12

        Rated current

         

        A

        630(250)

        Rated short-time withstand current and duration

        kA/s

        20(25)/4

        Rated peak withstand current

        kA

        50(63)

        Rated short-time power frequency withstand voltage

        Interphase and ground (dry test)

        kV/min

        42/1

        Fracture (dry test)

        kV/min

        48/1

        Phase to ground (wet test)

        kV/min

        30/1

        Fracture (wet test)

        kV/min

        36/1

         

        Lightning impulse withstand voltage

        Phase to ground

        kV

        75

        Fracture

        kV

        85

        Loop resistance

         

        μΩ

        ≤80

        Mechanical life

         

        Times

        3000

        Pollution level

         

         

        eClass

        Creepage distance

         

        mm

        ≥372


        Overall and installation dimensions


        国产精品揄拍100视频